Description
The Ei414 RadioLINK+ Fire/CO Alarm Interface connects Aico domestic alarms to external devices, ensuring comprehensive safety integration.
Key Features:
- Power Source: Mains powered with rechargeable lithium cell back-up.
- Compatibility: Interfaces with Telecare/Warden Call devices, sprinkler systems, and more.
- Wireless Connectivity: Uses RadioLINK+ wireless technology to connect with domestic alarms and accessories.
- Testing: Allows for simple testing of domestic and external systems.
- Interconnection: Connects wirelessly with all other Aico wireless interconnection products.
Why Use the Ei414 Alarm Interface?
Many properties have fire and carbon monoxide alarms, but these systems are often not connected to other life-saving devices. The Ei414 bridges this gap, ensuring comprehensive safety by connecting alarms with systems like Telecare, fire panels, and sprinkler systems. This integration enhances the overall safety of the occupants.
Systems Compatible with the Ei414
The Aico Ei414 RadioLINK+ Fire/CO Alarm Interface connects Aico smoke, heat, and carbon monoxide alarms with various external devices. This ensures quick and efficient lifesaving connections, enhancing occupant safety during fire or carbon monoxide incidents. It can connect with:
- Fire Panel Systems
- Telecare / Warden Call Systems
- Fire Suppression Systems
- Gas Shut Down Systems
- Plant Interface Systems
Operation of the Ei414 Fire/CO Alarm Interface
When domestic alarms activate, they send a signal using RadioLINK+ to the Ei414. The interface identifies the signal as a fire, carbon monoxide leak, or service requirement/fault. This signal is then relayed to the external device, which can transmit the alert to any connected devices or support centres.
Technical Specifications
- Supply Voltage: 230V AC or 10-30V DC.
- Current Rating: 230V AC = 1.6W 9mA, 10-30V DC = 1.8W 60mA.
- Operating Frequency: 868.499 MHz.
- RF Range: Over 100 meters in free space.
- RF Visual Indicator: Blue light indicates RF activity.
- Power Indicator: Green light indicates power presence.
- Alarm Indicator: Red light for fire, Red light for CO, Service Indicator: Red light.
- Mounting: Easily mounted onto a wall.
- Guarantee: 5 years.
- Outputs: Fire Alarm Relay (NO/NC), CO Alarm Relay (NO/NC), Fault Alarm Relay (NO/NC).
- Relay Contacts: All relays are rated 250V AC @ 5 Amp.
- Temperature Range: 0°C to 40°C. Storage: 0°C to 35°C (in a dry area).
- Humidity Range: 15% to 95% Relative Humidity non-condensing.
- Dimensions: 185mm x 90mm x 37mm.
- Weight: 300g.
- Performance: Complies with R&TTE, EMC, and LV Directives.